Working Conditions and Installation | |
Ambient Temperature | The allowable ambient temperature is not higher than+70°C and not lower than-45°C; (If the capacity is reduced by more than+40°C , the details must be negotiated with the manufacturer) |
Atmospheric Conditions | When the ambient temperature is 40°C, the relative humidity of the atmosphere does notexceed 50% and higher relative humidity is allowed at lower temperatures; e.g.,90% at 20°C,taking into account condensation on the product surfacedue to temperature changes. |
Class of Pollution | Class 3 |
Installation Category | III |
Magnetic Field for Installation | 1.The magnetic field atthe installation position shall not exceed 5 field in any direction; 2.In a medium without explosion risk, and without gas and conductive dust sufficient to corrode metal and damage insulation; 3.Where there is nowind or snow erosion. |
Installation Conditions | 1.Can be installed horizontally and vertically; 2.The installation site should be free of significant impact and vibration,and should not be installed in flammable and explosive places. |
Model | BAM5DC | ||||||
Breaker Current Frame | 250 | 315 | |||||
Rated Current(A) In | 63 80 100 125 140 160 180 200 225 250 | ||||||
Rated Insulation Voltage(V) Ui | 1500V | ||||||
Rated Impulse withstand Voltage(KV) Uimp | 12 | ||||||
Rated Voltage(V) | 2P Design | DC250V DC500V DC100V DC1500V | |||||
3P Design | DC1000V DC1250V DC1500V | ||||||
Type of Electric | DC | PV | DC | PV | |||
Rated Limit Short Current Breaking Capacity(KA) Icu | 2P Design | 15@DC1000V | 50@DC250 500V | 15@DC1000V | 50@DC250 500V | ||
5@DC1500V | 25@DC750 1000V | 5@DC1500V | 25@DC750 1000V | ||||
7.5@DC1500V | 7.5@DC1500V | ||||||
3P Design | 20@DC1500V | 25@DC750 1250V | 20@DC1500V | 25@DC750 1250V | |||
25@DC1500V | 25@DC1500V | ||||||
Rated Short Current Breaking Capacity(KA) Ics | 2P Design | 100% | |||||
3P Design | |||||||
Isolation Function | YES | ||||||
Using Cartegry Cat. | A | ||||||
Mechanism Life (times) | 20000 | ||||||
Electrical Life (times) | 1500 | ||||||
Overview Dimension(mm) | 200*107*135 |
Model | BAM5DC | ||||||
Breaker Current Frame | 400 | 630 | 800 | ||||
Rated Current(A) In | 250 315 350 400 | 400 500 630 | 630 700 800 | ||||
Rated Insulation Voltage(V) Ui | 1501V | ||||||
Rated Impulse withstand Voltage(KV) Uimp | 13 | ||||||
Rated Voltage(V) | 2P Design | DC250V DC500V DC100V DC1500V | |||||
3P Design | DC1000V DC1500V | ||||||
Type of Electric | DC | PV | DC | PV | DC | PV | |
Rated Limit Short Current Breaking Capacity(KA) Icu | 2P Design | 25@DC250 500V | 50@DC250 500V | 25@DC250 500V | 50@DC250 500V | 25@DC250 500V | 50@DC250 500V |
15@DC750 1000V | 25@DC750 1000V | 15@DC750 1000V | 25@DC750 1000V | 15@DC750 1000V | 25@DC750 1000V | ||
10@DC1500V | 10@DC1500V | 10@DC1500V | 10@DC1500V | 10@DC1500V | 10@DC1500V | ||
3P Design | 30@DC1000V | 40@DC1000V | 30@DC1000V | 40@DC1000V | 30@DC1000V | 40@DC1000V | |
25@DC1500V | 30@DC1500V | 25@DC1500V | 30@DC1500V | 25@DC1500V | 30@DC1500V | ||
Rated Short Current Breaking Capacity(KA) Ics | 2P Design | 101% | |||||
3P Design | |||||||
Isolation Function | YES | ||||||
Using Cartegry Cat. | A | ||||||
Mechanism Life (times) | 10000 | ||||||
Electrical Life (times) | 800 | ||||||
Overview Dimension(mm) | 310*182*156 |
DISTANCE (mm) | Model&Spec. | BAM5DC-250 | BAM5DC-315 | BAM5DC-400 | BAM5DC-630 | BAM5DC-800 |
A | 30 | 30 | ||||
B | 30 | 30 | ||||
C | 30 | 30 | ||||
D | 30 | 30 | ||||
E | 188 | 185 | ||||
F | 13 | 13 | ||||
G | 80 | 50 | ||||
H | 280 | 320 | ||||
I | 94 | 118 | ||||
J | 53 | 60 | ||||
4-ød | 2-ø4.5 | 4-ø4.5 |
BAW5DC Seriers MCCB Installation Section Area | |
Current(A) | Section Area(mm2) |
63 | 16 |
80 | 25 |
100 | 35 |
125/400 | 50 |
160 | 70 |
180/200/225 | 95 |
250 | 20×5 |
280/300/315 | 20×5×2 |
350/400 | 40×5 |
500630 | 40×8 |
700/800 | 40×5×2 |